Features
programmable controller 8 digital inputs 4 relay outputs 8A 4 NPN outputs 1A Ethernet, USB, IEX-2 2 RS232, 1 RS485 2 Wiegand interface RFM wireless interface (optional) EnOcean gateway (optional) 230V AC power supply
Dashboard presents new Cybro-3 features, and provide a quick test for both software and hardware components of the controller. It is a part of CyPro package, located in /CyPro-3/Examples/CybroDashboard/.
Cybro mobile app, HIQ Commander, can be used to monitor, control and configure any of your plc program (CyPro User Manual v51.pdf or or newer, feature Mobile application).
To get the app running, you need:
• Cybro-3 controller + plc program (see \Cybrotech\CyPro-3\Examples\
HIQ Commander Demo.cyp)
• mobile phone + HIQ Commander (v1.3.0 or later from https://play.google.com/store/)
Features
programmable controller 8 digital inputs 4 relay outputs 8A 4 NPN outputs 1A Ethernet, USB, IEX-2 2 RS232, 1 RS485 2 Wiegand interface RFM wireless interface (optional) EnOcean gateway (optional) 230V AC power supply
Technical specifications
Input type (ix00..ix07) | dry contact, internal pull-up 12V 2mA |
Galvanic isolation | none |
Output type (qx12..qx15) | NPN transistor 30V 1A |
Permanent load | 1.5A qx12+qx13 and 1.5A qx14+qx15 |
Protection | short circuit, overvoltage, overheating |
Galvanic isolation | none |
COM3 interface | RS485 (terminals) |
Galvanic isolation | none or 1kV (ISO) |
Cable length | 50 or 500m (ISO) |
Transmit/receive | automatic switching |
Wiegand input | active low, internal pull-up 3V3 1mA |
Timing | 20us min pulse, 20ms max spacing |
Power supply | 100..240VAC, 50/60Hz |
Power consumption | 1W no load, 10W max. |
IEX-2 power output | 24V 250mA |
Wiegand power output | 12V 500mA |
Total power output | 6W (IEX-2+Wiegand) |
Standards | EN 60730-1 |
Other specifications are common for all Cybro-3 models.
RS485 port depends on CPU version: | |
CYCPU3 v1.3 | COM1 |
CYCPU3 v1.4 | COM1 |
CYCPU3 v1.5 | COM3 |
CYCPU3 v1.7 | COM3 |
With older versions, RS485 is connected in parallel to the existing COM1. Newer versions have third, fully independent port. To check the version, remove top cover. It is printed on top of the pcb, above RUN led. |
Order Code
Cybro-3W-230 | 8 digital inputs, 4 relay outputs 8A, 4 NPN outputs 1A. 2 Wiegand interface, 1 RS485 interface (COM3), 230V AC power supply |
Options | |
– RFM | free-programmable radio |
– ENO | EnOcean gateway |
– ISO | galvanically isolated RS485 |