Features
programmable controller 10 opto-coupler inputs 24V 8 relay outputs 5A Ethernet, IEX-2, 2x RS-232
Technical specifications
System clock | 24MHz |
Instruction execution | 250ns per instruction |
Program memory | 64Kb for user program |
Data memory | 32Kb for user variables |
Data retention | 7 days |
Digital inputs | |
Input type | 24V, typ. 7mA, IX0-IX7: sink or source (PNP or NPN), |
Program memory | IX8-IX9: sink (PNP), opto isolated |
Digital outputs | |
Output type | relay contacts, normally open |
Load | 5A/250VAC |
RTC accuracy | typ. +-2 sec/day at 25°C |
IEX-2 bus (i/o modules) | |
Bus load | max. 31 modules |
Baud rate | 20, 50, 100 (default), 250, 500kbps |
Cable length | max. 500m |
Operating conditions | 0..50°C, 0..85% rh non-condensing |
Mounting | DIN rail (35mm) |
Dimension | 106x107x58mm |
Weight | 400g |
Degree of protection | IP20 |
Installation category | II |
Level of ambient pollution | 2 |
Standards | EN 61131-1, EN 61131-2, EN 50090-2-2 |
CyBro-2-230 | |
Power supply | 230VAC (100-240VAC), 50/60Hz |
Power consumption | typ. 4W (CPU, no external load) |
typ. 5W (CPU + 8 relays, no external load) | |
Power output | 24V max. 320mA (at 85..260VAC, max. 50°) |
24V max. 500mA (at 230..240VAC, max. 40°) |
CyBro-2-24 | |
Power supply | 24VDC (19-28VDC) |
Power consumption | typ. 4W (CPU, no external load) |
typ. 5W (CPU + 8 relays, no external load) | |
Power output | 2A |
Order Code
CYBRO-2-24-E | 24V power supply |
CYBRO-2-230-E | 230V power supply |