Features

IEX-2 module, touch operator panel LCD display 2×20 characters, white/blue temperature, humidity and light sensor IR receiver, beeper 1 switch/potentiometer input 1 temperature sensor input

Features

IEX-2 module, touch operator panel LCD display 2×20 characters, white/blue temperature, humidity and light sensor IR receiver, beeper 1 switch/potentiometer input 1 temperature sensor input

Technical specifications
Display LCD 2x20 characters
Characters size 3x5mm
Keys 5 touch keys, tactile feedback
Backlight blue LED, adjustable 0..100%
IR receiver RC5 36kHz, receiving distance 5m
Input type dry contact, internal pull-up 12V 2mA
analog input 0..10V (10 bit, 0..1023)
Temperature measurement range: 0°C to +50°C
error: ±0.5°C typ. (0°C to +50°C, backlight at 20%)
±2°C max. (0°C to +50°C)
resolution: 0.1°C (12 bit)
readout: 0.1°C (254 equals 25.4°C)
Humidity measurement range: 0..100% rh, non-condensing
error: ±2% rh @ 25°C
response time 15s
stability ±1% rh @ 50% rh in 5 years
resolution 1% (7 bit)
readout 1% rh (45 equals 45% rh)
External temperature sensor ES-P, ES-B or ES-W
Power supply 24V (18..28V), 50mA
Degree of protection IP20
Operating conditions 0..50°C, 0..85% rh non-condensing
Storage temperature -20..75°C
Mounting M4 installation box
Dimensions 144x80x7mm
Weight 200g
Level of ambient pollution 2
Standards EN 60730-1
Order Code
OP-8 operator panel
OP-8-CYR operator panel with cyrillic display