Features
programmable controller 12 opto-coupler inputs 24V 10 relay outputs 8A 4 universal input/outputs Ethernet, USB, IEX-2, 2x RS-232 RFM wireless interface (optional) EnOcean gateway (optional) 24V DC power supply
Dashboard presents new Cybro-3 features, and provide a quick test for both software and hardware components of the controller. It is a part of CyPro package, located in /CyPro-3/Examples/CybroDashboard/.
Features
programmable controller 12 opto-coupler inputs 24V 10 relay outputs 8A 4 universal input/outputs Ethernet, USB, IEX-2, 2x RS-232 RFM wireless interface (optional) EnOcean gateway (optional) 24V DC power supply
Technical specifications
Digital input (ix00..ix11): | 24V 7mA, opto isolated, bidirectional |
Digital output (qx00..qx09): | relay 8A/250VAC or 8A/30VDC resistive |
CPU board: | |
System clock | 100MHz, 10ns per instruction |
Watch dog | 100ms software, 250ms hardware |
Program memory | 896Kb for user program |
Data memory | 64Kb for user variables |
Data retention | typ. 7 days at 25°C |
RTC accuracy | typ. ±2 sec per day at 25°C |
COM1/COM2: | RS232, no galvanic isolation |
USB: | USB 2.0, no galvanic isolation |
Ethernet: | 10/100M |
Galvanic isolation | 1500V transformer |
IEX-2: | |
Bus load | 48 modules (Cybro + 47 IEX-2) |
Baud rate | 20, 50, 100 (default), 250, 500kbp |
Galvanic isolation none | none |
Cable length | 100m (100kbps, non-terminated) |
300m (100kbps, terminated) | |
500m (50kbps, terminated) | |
General: | |
Operating conditions | 0..50°C, 0..85% rh non-condensing |
Level of ambient pollution | 2 |
Power supply | 24V (18..28V) |
Power consumption | 50mA (no load) |
180mA (10 relays, 4x 10Vout) | |
IEX-2 power output | 24V 2A, limited by resettable fuse |
Mounting | DIN rail (35mm) |
Dimensions | 106x117x58mm |
Weight | 280g |
Degree of protection | IP20 |
Installation category | III |
Standards | EN 61010-1, EN 61010-2-201, EN 61131-2 |
Order Code
Cybro-3-24 | 12 opto-coupler inputs, 10 relay outputs 8A, 4 universal inputs/outputs, 24V DC power supply |
Options | |
– RFM | free-programmable radio |
– ENO | EnOcean gateway |
– ISO | galvanically isolated RS485 |
Notes: | |
– controller cannot have ENO and RFM options at the same time | |
– when ENO option is used, RS485 serial interface uses COM1 instead of COM3 port | |
– ISO option doesn’t make sense on controller without RS485 interface |