100,00 

50+

Features

wireless modbus relay remote controlled relay act as modbus RTU slave very long range, no hopping up to 8 relays per network protected private connection multiple addressable groups

Mounting

Device should not be installed inside the metal cabinet.
Distance from antenna to the nearest object should be at least 10cm.

Features

wireless modbus relay remote controlled relay act as modbus RTU slave very long range, no hopping up to 8 relays per network protected private connection multiple addressable groups

Technical specifications
Modbus
Address range 200..207
Relay mapping coil 1 (start address 00h)
Data bits & parity 8n1
Supported functions 01 – read coils
05 – write single coil
15 – write multiple coils
Relay output
Nominal rating 10A 250Vac (NO), 3A 250Vac (NC)
(resistive) 5A 30Vdc (NO), 3A 30Vdc (NC)
Radio
Frequency band ISM 868MHz (EU)
Subband L 866.8MHz, 25mW, 1% utility
Modulation FSK 38.4kbps 80kHz bandwidth
Listen before talk yes, delay limited to 20ms
Group address 32-bit, automatically generated
Connection time 10s power-on to network ready
Message delay 5ms from tx start to relay on
Output power 25mW
Operating range 3..300m with optical visibility
General
Power supply 230V, 50..60Hz, 1W
Terminals 0.25..1.5mm2
Operating conditions -20..+50°C, 0..85% rh nc
Storage temperature -40..+85°C
Dimensions 93x45x27mm, 86mm antenna
Weight 100g
Degree of protection IP20
Standards EN60730-1, EN300-220-2
Order Code
WR-1
Examples
Secure group